Heat Pump for Small Capacity Type J-II Series AJYA40LALH

Outdoor unit

Outdoor Unit :
AJYA40LALH
Download:
Catalogue

Features

  • High energy efficiency
  • Flexible systems for small- and medium-size buildings air conditioning

Capacity

Cooling  12.1 kW
Heating  13.6 kW


Specification
Rating Capacity range 4
Maximum Connectable Indoor Unit*1 7
Scroll
Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 12.1 kW
Heating 13.6 kW
Input Power Cooling 3.25 kW
Heating 3.17 kW
EER Cooling 3.72 W/W
COP Heating 4.29 W/W
Air flow late 6,200 m³/h
Sound pressure level*2 Cooling 50 dB(A)
Heating 52 dB(A)
Sound power level Cooling 66 dB(A)
Heating 66 dB(A)
Net Dimension Height 1,334 mm
Width 970 mm
Depth 370 mm
Net Weight 117 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 4.8 kg
Connection pipe
diameter
Liquid 9.52 mm
Gas 15.88 mm
Operation range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function may work when using it outside the operation range.
*Model number may change without prior notice
Dimensions

Outdoor Unit : AJYA40LALH

Outdoor unit