Heat Pump Modular type V-III TROPICAL Series AJY360LNLBHH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY126LNLBH
Outdoor Unit :
AJY126LNLBH
Outdoor Unit :
AJY108LNLBH
Download :
Catalogue

Features

  • Excellent energy saving
  • High design flexibility for various building air conditioning
  • Easy installation and maintenance
  • Energy saving technology that boosted operation efficiency
  • Heavy anti-corrosion treatment design
  • Powerful cooling capacity design

Capacity

Cooling  113.5 kW
Heating  127.5 kW


Specification

Rating Capacity Range 40
Maximum Connectable Indoor Unit*1 55
Indoor unit connectable capacity 56.8 - 147.5 kW
Scroll
Power source Phase 3-phase
Voltage ~400 V
Frequency 50,60 Hz
Capacity Cooling 113.5 kW
Heating 127.5 kW
Input Power Cooling 30.88 kW
Heating 30.99 kW
EER Cooling 3.68 W/W
COP Heating 4.11 W/W
Air Flow Rate 13000×3 m/³h
Sound Pressure Level*2 Cooling 64 dB(A)
Heating 66 dB(A)
Sound Power Level Cooling 85 dB(A)
Heating 86 dB(A)
Maximum external static pressure 82 Pa
Compresor motor output 11.0×3 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1690×3 mm
Width 1240×3 mm
Depth 765×3 mm
Net Weight 279×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Gas 41.27 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY126LNLBH / AJY126LNLBH / AJY108LNLBH

Outdoor unit